DOL 17
The CO2 sensor DOL 17 is used in connection with the SKOV climate and production computers for monitoring or control of the climate based on the CO2 content in the housing air. The auto-calibration procedure of the CO2 sensor compensates for ageing of the infrared source and guarantees high reliability, long term stability and eliminates the need of periodical recalibration.
To see data sheet, go to Download.
| Measuring principle |
None-Dispersive Infrared Technology (NDIR) |
Accuracy at 20°C (68°F) and 1013 mbar |
0...7000 ppm < ± (50 ppm +5% of measuring value) 7000...10000 ppm < ± (100 ppm +10% of measuring value) |
| Response time τ63 1) |
< 120 sec. |
| Temperature dependence |
Typically 2 ppm CO2/°C |
| Long term stability |
Typically 20 ppm / year |
| Sample rate |
Approx. 30 sec. |
| 0...10000 ppm |
0-10 V -1 mA < IL < 1 mA |
| Supply voltage SELV |
24 V AC ± 20% 15-35 V DC SELV = Safety Extra Low Voltage |
| Power requirement |
< 3 W |
| Warm up time |
< 5 min. |
| Encapsulation / protection class |
PC / IP54 |
| Electrical connection |
M12 plug |
| Electromagnetic compatibility |
EN 61000-6-3 ÖVE EN61326-1+A1+A2:05.2002 EN 61000-6-1 FCC Part 15 ICES-003 ClassB |
| Operation temperature and conditions |
-20...60°C (-4...140°F) 0...100% RH |
| Storage temperature and conditions |
-20...60°C (-4...140°F) 0...95% RH (non-condensing) |